30 Reference & Installation Manual
Section [510]: Download from Memory Key (PMC-3) to DGP2-641R.
Section [520]: Upload from DGP2-641R to Memory Key (PMC-3).
Section [007]: Confidential Mode Timer
____/____/____ (005 to 255 seconds) Default: 120 secs.
Section [008]: Door Unlocked Period
____/____/____ (000 to 255 seconds) Default: 005 secs.
Section [009]: Door Unlocked Period Extension
____/____/____ (000 to 255 seconds added to section [008]) Default: 015 secs.
Section [010]: Door Left Open Interval
____/____/____ (000 to 255 seconds) Default: 060 secs.
Section [011]: Door Left Open Pre-Alarm Timer
____/____/____ (000 to 255 seconds) Default: 015 secs.
Section [012]: Beep Timer for Door Left Open Alarm
____/____/____ (000 to 255 seconds) Default: 005 secs.
Section [013]: Beep Timer for Door Forced Open Alarm
____/____/____ (000 to 255 seconds) Default: 005 secs.
Section [017]: Door Unlocked Schedule
Start Time End Time Days (turn ON or OFF)
SMTWTFSH
Schedule A: ___ ___: ___ ___ ___ ___: ___ ___ 1 2 345678
Schedule B: ___ ___: ___ ___ ___ ___: ___ ___ 1 2 345678
DGP2641R_ei00.fm Page 30 Thursday, July 22, 2004 4:16 PM