20 Reference & Installation Manual
reader to beep a certain time before the end of the Door Left Open
Interval to alert users that the Access Control door was left open
and will generate an Access Alarm if it is not closed. The Pre-
Alarm beeps slower than the Door Left Open Alarm (about twice
every second). Program the Pre-Alarm timer in section [011].
Option [3] OFF = The Pre-Alarm will not be generated
Option [3] ON = Pre-Alarm is enabled (default)
5.3.4 Door Left Open Pre-Alarm Timer
S
ECTION [011]
This timer will trigger the Door Left Open Pre-Alarm before the
end of the Door Left Open Interval (see section 5.3.3 above).
For example, if 60 seconds is programmed in section [010] and
15 seconds is programmed in section [011], the reader will start
beeping after the door has been open for 45 seconds (60 - 15 =
45 seconds). Enter any value between 001 and 255 to
determine the seconds before the expiry of the Door Left Open
Interval that the reader will beep. Default = 15 seconds.
Figure 6: Pre-Alarm example
5.3.5 Door Left Open Alarm Feedback
S
ECTION [004]: OPTIONS [5] AND [6]
An Access Control door is programmed with a Door Left Open
Interval (see section 5.3.2 on page 19). Once this interval has
expired, the Door Left Open Alarm can be either audible or silent
DGP2641R_ei00.fm Page 20 Thursday, July 22, 2004 4:16 PM